Installation Manual - Aurum Controller
The Aurum has been discontinued and is no longer sold for new projects. This documentation remains available to support existing installations. For new projects or replacements, contact the Iongrade sales team.
This manual guides the designer or installer through the physical installation and the electrical connections of the Aurum access controller.
Power Supply

The controller must be powered with 12 VDC ±5%. Consumption, without readers and additional modules, is 120 mA.
| Specification | Value |
|---|---|
| Supply voltage | 12 VDC ±5% |
| Consumption (without peripherals) | 120 mA |
Use a regulated power supply sized to support the controller and all connected peripherals (readers, locks, etc.).
Card Reader Connections

The Aurum controller has interfaces for three readers of the ABATrack or Wiegand type.
Each reader has a jumper for selecting the supply voltage, with options of 5 VDC or 12 VDC.
Reader Voltage Selection
To select the voltage of each reader, use the jumpers:
| Jumper | Reader | Options |
|---|---|---|
| JP1 | Reader 1 | 5 VDC or 12 VDC |
| JP2 | Reader 2 | 5 VDC or 12 VDC |
| JP3 | Reader 3 | 5 VDC or 12 VDC |
The positions of each voltage option (12V or 5V) are identified on the printed circuit board, next to the jumpers.
Sensor and Command Button Connections

The signal inputs must be used for:
- REX (Request to Exit): command buttons
- DOOR SWITCH: door state sensors
- PAS SWITCH: turnstile rotation sensors
Input Pinout
| Terminal | Function |
|---|---|
| PAS/DOOR 1 | Passage/door sensor - Channel 1 |
| REX 1 | Exit button - Channel 1 |
| PAS/DOOR 2 | Passage/door sensor - Channel 2 |
| REX 2 | Exit button - Channel 2 |
| COMUM | Common (GND) |
The sensors connected to these inputs must be of the dry contact type, potential-free.
Command Relay Connections

The controller has four command relays with the following capacities:
| Specification | Value |
|---|---|
| AC load | 1A / 120VAC |
| DC load | 2A / 30VDC |
Observe these limits to ensure the integrity and service life of the relay contacts.
Relay Function
The LOCK 1 or LOCK 2 relays are triggered when the controller grants access; the ALRM 1 or ALRM 2 relays are triggered when an access request is denied. The activation time settings are made during the controller configuration stage.
| Relay | Channel | Function |
|---|---|---|
| LOCK 1 | Channel 1 | Triggered when access is granted |
| ALRM 1 | Channel 1 | Triggered on denied access |
| LOCK 2 | Channel 2 | Triggered when access is granted |
| ALRM 2 | Channel 2 | Triggered on denied access |
Relay Pinout
Each relay has three terminals:
| Terminal | Function |
|---|---|
| NF | Normally Closed |
| C | Common |
| NA | Normally Open |
Serial Ports (UARTs)

The controller has three serial communication ports. The UART1 and UART2 ports are available for connecting various configurable devices. The UART VOC serial port is used for communication with the voice module.
UART Jumper Configuration
The controller has several jumpers for configuring the electrical level of the UARTs. On the printed circuit board, next to the jumpers, the correct positions for RS232 or TTL are identified.
UART 1:
| Parameter | Options | Jumper(s) |
|---|---|---|
| Voltage for the device | 5 VDC / 3.3 VDC | JP13 |
| Electrical level | TTL / RS232 | JP4, JP5, JP10, and JP11 |
UART 2:
| Parameter | Options | Jumper(s) |
|---|---|---|
| Voltage for the device | 5 VDC / 3.3 VDC | JP12 |
| Electrical level | TTL / RS232 | JP6, JP7, JP18, and JP9 |
UART VOC:
This port does not require jumper configuration. The signal level is TTL at 3.3 VDC.
Serial Connector Pinout
| Pin | Signal |
|---|---|
| 1 | +VCC |
| 2 | TX |
| 3 | RX |
| 4 | GND |
LCD Display

The controller is ready for the connection of a display module (LCD) with I2C communication. The electrical level of the signals is TTL at 5 VDC.
| Pin | Signal |
|---|---|
| 1 | GND |
| 2 | +5VCC |
| 3 | SCL |
| 4 | SDA |
Buttons and Indicators

RESET button — forces the controller to restart (boot). Press it quickly to exit configuration mode.
MODE button — puts the controller into configuration mode. Press and hold for 5 seconds.
STATUS LED — provides information about the general state of communication.
Reading the STATUS LED
When the controller is in operation mode, the STATUS LED provides information about the general state of communication. Every two seconds, a series of up to four quick blinks begins:
| Blink | Meaning |
|---|---|
| 1 | Controller in operation mode |
| 2 | Network connection (Ethernet/WiFi) OK |
| 3 | Connection to the system Broker OK |
| 4 | Communication with the server OK |
When four blinks are counted in each cycle, the situation is normal. This check is very helpful during installation and maintenance to locate communication failures.
Starting the Configuration
The Aurum controller is configured through a browser. To start the configuration, follow the steps below.
1. Enable Configuration Mode
- Press and hold the MODE button for 5 seconds.
- The controller automatically starts in Configuration mode.
- The STATUS LED keeps blinking quickly, indicating that the mode is active.
- The controller activates a WiFi access point (AP mode) and starts accepting client connections.
2. Connect to the Controller's WiFi Network
The WiFi network created by the controller has a unique and exclusive name (SSID) for each controller:
- Format:
aurum+ identification code - Examples:
aurum7512208F,aurum89C0CF6A
3. Access the Configuration Interface
-
Connect to the controller's WiFi network.
-
Open the browser and go to:
http://192.168.4.1 -
Enter the default credentials:
- User:
admin - Password:
aurumpwd
- User:
From here on, see the Operation Manual to configure each controller screen.
Installation Recommendations
- Location: install the controller in a place protected from the weather.
- Ventilation: ensure adequate ventilation for heat dissipation.
- Grounding: connect the grounding system properly.
- Cabling: use shielded cables for readers in environments with interference.
- Protection: consider using surge protectors on the power supply.
Next Steps
After completing the physical installation, see the Operation Manual to configure the controller.